Typical Configuration #
Micro-module data centers are classified as Micro-module A and Micro-module B based on differences in their power supply and distribution systems:

- Micro-module A: Integrated UPS added to the list; lead-acid batteries/lithium batteries removed from the list; lead-acid batteries added to the list; air conditioning units added to the list.
- Micro-module B: UPS and lead-acid batteries/lithium batteries removed from the list; power distribution cabinets and air conditioning units added to the list.
Table 3-1 Typical Configurations #
|
Micro-module Scenarios |
Inside the micro-module |
Outside the Micro-Module |
|---|---|---|
|
Micro-Module A (Lead-Acid Battery Included) |
Integrated UPS systems, smart temperature control products, lead-acid batteries, cabinets, aisles, and structural components |
– |
|
Micro-module A (Lead-acid/Lithium-ion Battery Removal) |
Integrated UPS systems, smart temperature control products, server cabinets, aisles, and structural components |
Lead-acid Batteries / Lithium-ion Batteries |
|
Micro-Module B (Integrated Power Distribution Cabinet) |
Integrated Power Distribution Cabinets, Smart Temperature Control Products, Cabinets, Aisles, and Structural Components |
UPS, Lead-Acid Batteries/Lithium-Ion Batteries |
|
Micro-Module B (Precision Power Distribution Cabinet) |
Precision Power Distribution Cabinets, Smart Temperature Control Products, Cabinets, Aisles, and Structural Components |
UPS, Lead-Acid Batteries/Lithium-Ion Batteries, and Smart Temperature Control Products Distribution Boxes |
|
Micro-Module B (NMW) |
NMW, Smart Temperature Control Products, Cabinets, Aisles, and Structural Components |
UPS, Lead-Acid Batteries/Lithium-Ion Batteries, and Smart Temperature Control Products Distribution Boxes |
Note #
Equipment inside and outside the micro-module can be located in the same room or in two separate rooms. If located in the same room, the module employs a sealed hot-aisle configuration to maintain the battery’s ambient temperature.
Table 3-2 Layout Options #
|
Micro-module Scenarios |
N+1 Scenarios |
2N Scenarios |
|---|---|---|
|
Micro-Module A (Lead-Acid Battery Included) |
||
|
Micro-module A (Lead-acid/Lithium-ion Battery Removal) |
||
|
Micro-Module B (Integrated Power Distribution Cabinet/Precision Power Distribution Cabinet) |
||
|
Micro-Module B (NMW Smart Busbar) |
Table 3-3 Power Distribution Specifications #
|
Micro-module Scenarios |
Power Supply and Distribution System |
Parameters |
|---|---|---|
|
Micro-Module A |
Integrated UPS |
|
|
Micro-Module B |
Integrated Power Distribution Cabinet |
160A/250A power distribution inputs (IT input circuit breakers and smart temperature control product input circuit breakers), 48 IT power distribution circuits, 16 smart temperature control product power distribution circuits, and 6 dual-input and 3 single-input lighting power distribution circuits; supports 95 kW/148.5 kW of IT load. |
|
Precision Power Distribution Cabinet |
160A/250A/400A/630A power distribution inputs, supporting up to 144 IT power distribution circuits and 95 kW/148.5 kW/235 kW/310 kW of IT load. |
|
|
Smart Busbar 2.0 |
250A/400A power distribution input, supporting 123 kW/198 kW of IT loads. |
|
|
Smart Busbar 2.1 |
|