Precision Air Conditioning Maintenance Service
VERHI precision air conditioning service for inspection, maintenance, repair, retrofit and modernisation projects.

Defined Scope
Inspection, maintenance, repair and retrofit work is defined against the installed system.
System History
Fault history and operating records are used to plan the service correctly.
Parts Control
Required spares and compatibility are confirmed before service work begins.
Site Reporting
Service results, residual risk and recommended follow-up are documented.
Technical Specifications
|
Model / cooling type |
BPCM5(cooling only/heating/constant temperature and humidity) |
|---|---|
|
Total cooling capacity (kW) |
5.5 |
|
Sensible cooling capacity (kW) |
5.3 |
|
Airflow (m3/h) |
2600 |
|
Cooling type |
air-cooled |
|
Operating voltage |
220VAC, 50Hz(L+N+PE) |
|
Number of fans |
1 |
|
Number of compressors |
1 |
|
Heating capacity (kW) |
-/4/4 |
|
Humidification capacity (kg/h) |
-/-/3 |
|
Full-load current (A) |
7.5/12.2/12.2 |
|
Communication interface |
RS485 |
|
Installation method (base ≥150 mm) |
vertical installation, installation base≥150mm |
|
Unit weight (kg) |
90 |
|
Unit dimensions (HxWxD, mm) |
1750*510*400mm |
|
Operating ambient temperature (°C) |
indoor: 0~40; outdoor: standard type, -15~+45; low-temperature type, -34~+45 |
|
Operating ambient humidity (RH) |
30%~80% |
|
Altitude (m) |
<1000, derate above 1000 m |
|
Model |
BPNEW5 |
|
Operating voltage range |
220VAC±10%, 50Hz(L+N+PE) |
|
Full-load current (A) |
0.8 |
|
Unit weight (kg) |
40 |
|
Unit dimensions (HxWxD, mm) |
662*785*350 |
|
Operating environment (°C) |
-15~+45; -34~+45(requires optional low-temperature kit) |
|
Protection rating |
IPX4 |
|
Installation method |
horizontal airflow installation |
Precision Air Conditioning Maintenance Service
Related Products
Related content
Technical Support
Installation and Operation
Software Download
Product Announcement
Technical Case Studies